Electrical
Updated Aug 18, 2026

Voltage Drop Calculator

Calculate voltage drop in a wire run. Supports AWG and mm^2 conductors, copper and aluminum, single and three-phase circuits.

Understanding Voltage Drop

Voltage drop is the loss of voltage along a conductor caused by the wire's resistance. It matters because undersized wire wastes energy as heat, dims lights, makes motors run hot, and can cause code-compliant circuits to fail in real-world use. The National Electrical Code recommends keeping voltage drop under 3% for branch circuits and 5% combined with feeders.

Single-Phase Voltage Drop

Voltage drop increases with current and one-way distance, and decreases with larger conductors. The standard formula uses circular mils (CM) for wire area:

Vdrop=2×K×I×LCM

K is the material resistivity constant: 12.9 for copper, 21.2 for aluminum. L is one-way distance in feet. I is current in amps. The factor of 2 accounts for the hot and neutral conductors.

Three-Phase Voltage Drop

Vdrop=√3×K×I×LCM

AWG to Circular Mils

AWGCircular Milsmm2Typical Use
144,1072.0815 A lighting
126,5303.3120 A outlets
1010,3805.2630 A dryer
816,5108.3740 A range
626,24013.350-60 A sub-panel
441,74021.285 A feeders
266,36033.6100 A service
4/0211,600107200 A service
Distance Doubles Drop
Voltage drop scales linearly with round-trip distance. Doubling the run from 50 ft to 100 ft doubles the drop. If you are close to the 3% limit, upsize one gauge per 25-50 feet of extra run, depending on current.

NEC Recommended Drop Limits

  • 3% maximum on branch circuits (outlets, lights, appliances) per NEC 210.19(A) Informational Note 4.
  • 2% maximum on feeders when branch drop is at 3%, for a combined limit of 5% (NEC 215.2(A)(1) Informational Note 2).
  • 5% maximum total from service entry to the farthest outlet, to ensure sensitive electronics and motors receive rated voltage.
Aluminum Requires Upsizing
Aluminum has 1.6x the resistivity of copper, so the equivalent aluminum conductor is typically 2 AWG sizes larger. For a 100 A service, copper is 3 AWG but aluminum must be 1 AWG. Always verify with your local AHJ and use only anti-oxidant compound at aluminum terminations.

Frequently Asked Questions