Electrical
Updated Aug 23, 2026

Breaker Size Calculator

Determine the correct breaker size for a load using NEC 125% rule. Supports watts or amps input and recommends a wire gauge.

How to Calculate Circuit Breaker Size

A circuit breaker has one job: to open (trip) before the wire in the circuit overheats dangerously. It protects the wire, not the appliance. Sizing a breaker correctly is critical for safety - undersized breakers trip on normal loads and create pressure to bypass the protection; oversized breakers fail to trip before the wire melts, potentially starting fires inside walls.

This calculator applies NEC 210.20(A) rules for continuous loads (125% factor), non-continuous loads (100% factor), and motor branch circuits (250% factor per NEC 430.52), then rounds up to standard breaker sizes listed in NEC 240.6(A).

Core Formula: Watts to Amps

The fundamental relationship is Ohm's Law adapted for AC power:

Amps=WattsVolts

For three-phase circuits:

Amps=WattsVolts×√3×PF

Continuous vs Non-Continuous Loads

The NEC defines a continuous load as one where the maximum current is expected to continue for 3 hours or more. This distinction matters because breakers are designed to carry 80% of their rating continuously. Per NEC 210.20(A), the breaker and feeder wire must be sized to 125% of the continuous load plus 100% of the non-continuous load:

Breaker Amps=(Continuous×1.25)+Non-Continuous

Load Type Examples

LoadTypeFactor
Store lightingContinuous×1.25
Residential lightingMixedTypically ×1.0
EV ChargerContinuous×1.25
Electric water heaterContinuous×1.25
Pool pumpContinuous×1.25
Electric dryerNon-continuous×1.0
Range / OvenNon-continuous×1.0
MicrowaveNon-continuous×1.0
Motor (branch)Motor×2.5 (Table 430.52)
The 80% Rule Explained
Standard breakers are tested to carry 100% of their rating briefly but only 80% continuously (for over 3 hours) without nuisance tripping from heat buildup. The 125% upsize is the mathematical inverse: 1 divided by 0.80 equals 1.25. This accounts for sustained heating.

Motor Branch Circuit Sizing (NEC 430.52)

Motors draw 5-7x their running current during startup (inrush current). A standard breaker sized to running current would trip every time the motor starts. NEC 430.52 solves this by allowing the branch breaker to be 250% of the motor full-load amperage (FLA). The motor itself is protected separately by overload relays or built-in thermal protection.

Motor Breaker=Motor FLA×2.5

The conductors, however, are sized at 125% of the FLA per NEC 430.22. This is why motor circuits have small wires but large breakers.

Standard Breaker Sizes (NEC 240.6)

Breakers are manufactured in specific standard sizes. After calculating your adjusted load amps, round UP to the next standard size:

15 A
20 A
25 A
30 A
35 A
40 A
45 A
50 A
60 A
70 A
80 A
90 A
100 A
125 A
150 A
175 A
200 A
225 A
250 A
300 A

Common Residential Breakers by Circuit

CircuitBreakerWire (Cu)
Lighting, general receptacles15 A14 AWG
Kitchen, bath GFCI20 A12 AWG
Dishwasher15-20 A14-12 AWG
Water heater (4500W/240V)30 A10 AWG
Electric dryer30 A10 AWG
Electric range40-50 A8-6 AWG
AC compressor (3-ton)30-40 A10-8 AWG
EV charger (Level 2, 48A)60 A6 AWG
100A subpanel feeder100 A3 AWG
Never Oversize the Breaker
The single most dangerous mistake in home electrical work is installing a larger breaker because the current one keeps tripping. The breaker is not the problem - the overload is. Installing a 20 A breaker on 14 AWG wire (rated for 15 A) means the wire will reach 160% of its rated capacity before the breaker trips, potentially igniting the wire insulation inside the wall.

Worked Example: Water Heater

Size a circuit for a 4,500 W electric water heater on 240V:

  1. Amps - 4500 / 240 = 18.75 A
  2. Type - Continuous (runs more than 3 hours when heating)
  3. Factor - 18.75 × 1.25 = 23.4 A
  4. Next standard breaker - 25 A (or 30 A for margin)
  5. Wire size - 10 AWG copper THHN (30 A ampacity at 75C)

Most installations use a 30 A breaker with 10 AWG for margin, even though 25 A technically works. The cost difference is negligible and startup tolerance is better.

Worked Example: EV Charger

Size a circuit for a Level 2 EV charger rated 48 A at 240 V:

  1. Charger rating - 48 A (11.5 kW)
  2. Type - Continuous (charging 6+ hours)
  3. Factor - 48 × 1.25 = 60 A
  4. Breaker - 60 A dedicated 2-pole
  5. Wire size - 6 AWG copper THHN (65 A ampacity at 75C)

Power Factor and 3-Phase Systems

Resistive loads (heaters, incandescent bulbs, electric stoves) have a power factor (PF) of 1.0 - volts times amps equals watts exactly. Inductive loads (motors, fluorescent ballasts, transformers) have PF below 1.0 because current lags voltage. The apparent power (VA) is always larger than real power (watts) by the reciprocal of PF.

LoadTypical PF
Resistive heater1.00
Incandescent light1.00
LED light (modern)0.90-0.95
Fluorescent ballast0.80-0.90
Induction motor0.75-0.85
Welder / arc0.30-0.60
Breaker Protects the Wire, Not the Appliance
A 20 amp breaker tripping on a 15 amp appliance does not mean the appliance is fine - it means something in the circuit is drawing more than 20 amps. Check appliance condition, measure actual draw with a clamp meter, or check for a short before considering circuit changes. Nuisance tripping almost always indicates a real problem.

Frequently Asked Questions